• DocumentCode
    3011709
  • Title

    Principal failure cases on distribution switchgear using in the 22.9kV-y distribution system

  • Author

    Tae-Ho Kwon ; Chong-Eun Cho ; Jong-Man Joung ; Dong-Myung Kim

  • Author_Institution
    Facility Diagnosis Center, Korea Electr. Power Corp., Daejeon, South Korea
  • fYear
    2012
  • fDate
    23-27 Sept. 2012
  • Firstpage
    1032
  • Lastpage
    1034
  • Abstract
    The faults of the pole mounted switchgears and the pad mounted switchgears in the Korea Electric Power Corporation (KEPCO) distribution system that have occurred over the last one year have been analyzed. The result has shown that, in the case of the pole mounted switchgear, 40% of the faults were caused by the bushing part, and, in the case of the pad mounted switchgear, the breakdown of the internal insulators accounted for the 24% of the faults. This research paper will present the causes of the faults through detailed analyses with regard to the principal failure of the switchgears.
  • Keywords
    bushings; poles and towers; power distribution faults; switchgear; KEPCO distribution system; Korea Electric Power Corporation; distribution switchgear; internal insulators breakdown; pad mounted switchgears; pole mounted switchgears; switchgear principal failure; voltage 22.9 kV; Circuit faults; Electron tubes; Insulators; Porcelain; Surface cracks; Switchgear; BMC; bushing; crack; insulator; moisture absorption; switchgear;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
  • Conference_Location
    Bali
  • Print_ISBN
    978-1-4673-1019-2
  • Type

    conf

  • DOI
    10.1109/CMD.2012.6416331
  • Filename
    6416331