Principal failure cases on distribution switchgear using in the 22.9kV-y distribution system
Author
Tae-Ho Kwon ; Chong-Eun Cho ; Jong-Man Joung ; Dong-Myung Kim
Author_Institution
Facility Diagnosis Center, Korea Electr. Power Corp., Daejeon, South Korea
fYear
2012
fDate
23-27 Sept. 2012
Firstpage
1032
Lastpage
1034
Abstract
The faults of the pole mounted switchgears and the pad mounted switchgears in the Korea Electric Power Corporation (KEPCO) distribution system that have occurred over the last one year have been analyzed. The result has shown that, in the case of the pole mounted switchgear, 40% of the faults were caused by the bushing part, and, in the case of the pad mounted switchgear, the breakdown of the internal insulators accounted for the 24% of the faults. This research paper will present the causes of the faults through detailed analyses with regard to the principal failure of the switchgears.
Keywords
bushings; poles and towers; power distribution faults; switchgear; KEPCO distribution system; Korea Electric Power Corporation; distribution switchgear; internal insulators breakdown; pad mounted switchgears; pole mounted switchgears; switchgear principal failure; voltage 22.9 kV; Circuit faults; Electron tubes; Insulators; Porcelain; Surface cracks; Switchgear; BMC; bushing; crack; insulator; moisture absorption; switchgear;