DocumentCode
3012913
Title
Simplified Method for the measurement of loss angle of a high voltage transformer
Author
Chattopadhyay, S. ; Mazumder, K.B. ; Bera, S.C.
Author_Institution
Dept. of Electr. Eng., Nat. Inst. of Tech. Teachers´´ Training & Res., Kolkata, India
Volume
3
fYear
2005
fDate
27-29 Sept. 2005
Firstpage
2148
Abstract
Measurement of loss angle of a transformer insulating material and its winding capacitance between primary and secondary windings or between windings and ground by bridge technique may suffer from errors due to the effect of stray capacitance between the bridge output lead wires as well as between the lead wires and ground. The conventional Wagner-earth technique may be used to minimise this effect. But one disadvantage of this technique may be the requirement of several repetitions of bridge balance and Wagner earth balance in each observation. In the present paper a modified operational amplifier based Schering bridge network has been proposed, where the effect of stray capacitance may be assumed to be negligible. Moreover, the bridge sensitivity may be adjusted by a linear potentiometer. The experimental work was performed with 33/3.3 kV transformers in the field at 33 kV substation. The dissipation factor for the adjustable value of the bridge sensitivity factor potentiometer with the change of high voltage at power frequency were obtained and reported. These experimental results appear to reveal the satisfactory performance of the bridge network.
Keywords
bridge circuits; insulating materials; operational amplifiers; potentiometers; power transformer insulation; transformer substations; transformer windings; 3.3 kV; 33 kV; Schering bridge network; Wagner-earth technique; bridge network; bridge sensitivity factor potentiometer; dissipation factor; high voltage transformer loss angle; linear potentiometer; operational amplifier; substation; transformer insulating material; winding capacitance; Bridge circuits; Cable insulation; Capacitance measurement; Earth; Goniometers; Loss measurement; Potentiometers; Power transformer insulation; Voltage transformers; Wires;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Machines and Systems, 2005. ICEMS 2005. Proceedings of the Eighth International Conference on
Print_ISBN
7-5062-7407-8
Type
conf
DOI
10.1109/ICEMS.2005.202946
Filename
1575143
Link To Document