DocumentCode
3013550
Title
On-line and on-site PD monitoring and diagnosis of power transformer
Author
Chun-she Xu ; Zhen-Quan Sun ; Guan-Jun Zhang
Author_Institution
Sch. of Electr. Eng., Xi´an Jiaotong Univ., Xian, China
fYear
2012
fDate
23-27 Sept. 2012
Firstpage
293
Lastpage
296
Abstract
Assessing the insulation condition of high-voltage transformers is essential for repairing and maintaining based on condition of equipment. For the instant diagnostic examination of PD with oil-paper insulated transformers, basically physical method directly related to PD is currently used electric signals. Based on advanced sensor technology, PD detectors with enhanced options for discriminating disturbances were carried out on-site and on-line. PD values condition changes of the insulation system can early be identified and evaluated with simple trending. Consequently, PD monitoring and diagnosis systems allow conditioned based maintenance strategies, serve asset appraisements and permit continuous risk assessment. The reliability and safety of the HV equipment and the system operation of the power network can be increased. The application of on-line and on site PD diagnosis of power transformers in service is a powerful tool to detect defects in the coil insulation. The approach with long term monitoring with remote access through substation communications or the web is important for the lifetime management of ageing transformers The techniques are described, together with cased studies of their application on the engineering practice field.
Keywords
ageing; maintenance engineering; paper; partial discharge measurement; potential transformers; power transformer insulation; reliability; risk management; safety; substations; transformer oil; HV equipment reliability; PD detectors; PD diagnostic examination; advanced sensor technology; coil insulation; conditioned based maintenance strategy; continuous risk assessment; defect detection; electric signals; high-voltage transformers; insulation condition assessment; lifetime management; oil-paper insulated transformers; on-site PD monitoring; online PD monitoring; power network; power transformer diagnosis system; substation communications; transformer ageing; Current measurement; Insulation; Monitoring; Partial discharge measurement; Partial discharges; Power transformer insulation; on site; online; partial discharge; transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location
Bali
Print_ISBN
978-1-4673-1019-2
Type
conf
DOI
10.1109/CMD.2012.6416434
Filename
6416434
Link To Document