• DocumentCode
    3024256
  • Title

    Modeling of automatic local controllers in three phase load flow calculation

  • Author

    Dzafic, Izudin ; Mohapatra, Prasant ; Neisius, Hans-Theo

  • Author_Institution
    Siemens AG, Nuremberg, Germany
  • fYear
    2011
  • fDate
    17-19 Jan. 2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper describes the modeling of automatically operated local controllers, based on the scheduled, measured or calculated values of the locally affected network equipment in real time operation of Distribution Management System - Control Center. The model presented is operated in unbalanced, unsymmetrical distribution networks and analyzed in phase domain. Simulated Locally controlled equipment includes various types of Transformer on load tap changers (LTC), Voltage Regulators and Shunts (Capacitors and Reactors). The modeling considers all control parameters with the special consideration of different phase types of the equipment and measurements, transformer connection types, and operation in unbalanced networks. As an addition to previous works in this area, specific and practical problems and considerations to Capacitor flow control, LTC reverse control with Distribution Generation, Parallel and Looped transformer operation are presented.
  • Keywords
    distribution networks; power system management; automatic local controllers; distribution management system; load tap changers; locally affected network equipment; three phase load flow calculation; Capacitors; Load flow; Load modeling; Reactive power; Regulators; Switches; Voltage control; Auto-reversible actions; Power regulators; Voltage regulators modeling;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies (ISGT), 2011 IEEE PES
  • Conference_Location
    Hilton Anaheim, CA
  • Print_ISBN
    978-1-61284-218-9
  • Electronic_ISBN
    978-1-61284-219-6
  • Type

    conf

  • DOI
    10.1109/ISGT.2011.5759196
  • Filename
    5759196