DocumentCode
303444
Title
Moisture dynamic measurements of transformer board using a three-wavelength dielectrometry sensor
Author
Du, Y. ; Zahn, M. ; Mamishev, A.V. ; Schlicker, AndD E.
Author_Institution
Dept. of Electr. Eng. & Comput. Sci., MIT, Cambridge, MA, USA
Volume
1
fYear
1996
fDate
16-19 Jun 1996
Firstpage
53
Abstract
The spatial distribution of dielectric permittivity and conductivity of an insulating medium affects the quasistatic distribution of the electric field. Multiple wavelength interdigital sensors using the imposed frequency-wavenumber (ω-k) dielectrometry technique can measure complex permittivity distributions in dielectrics. Measurements of oil-free and oil-impregnated pressboard transformer insulation using a three-wavelength sensor with changes in ambient moisture concentration are presented. With a calibrated mapping relating conductivity and permittivity to moisture concentration in oil-impregnated pressboard, the spatial distribution of moisture can be measured
Keywords
insulation testing; ambient moisture concentration; calibrated mapping; dielectric conductivity; dielectric permittivity; insulating medium; insulation breakdown tests; moisture dynamic measurements; pressboard transformer insulation; quasistatic electric field distribution; spatial distribution; three-wavelength dielectrometry sensor; Conductivity; Dielectrics; Electrodes; Frequency; Humidity; Moisture measurement; Temperature sensors; Testing; Voltage; Wavelength measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location
Montreal, Que.
ISSN
1089-084X
Print_ISBN
0-7803-3531-7
Type
conf
DOI
10.1109/ELINSL.1996.549281
Filename
549281
Link To Document