Title :
Effect of humidity on the breakdown of air gaps under oscillatory switching impulse voltages
Author :
Bharadwaj, Raj Mohan ; Prabhakar, B.R.
Author_Institution :
Dept. of High Voltage Eng., Indian Inst. of Sci., Bangalore, India
Abstract :
Experimental investigations were carried out to study the effect of humidity on the breakdown of rod-plane gaps subjected to both unidirectional and bidirectional oscillatory switching impulse voltages. The humidity ranged from 14.1-36 gm/m3 at a constant temperature of 40°C. The gaps were subjected to unidirectional 5.3, 10, 19 kHz and bidirectional 4.2, 10, 20 kHz oscillatory switching impulse voltages. The gap distance was varied from 8 to 30 cm. The experiments were carried out in a controlled atmospheric room. The results indicate an increase in breakdown strength with increase in humidity. The results are of great relevance at atmospheric conditions existing in tropical countries
Keywords :
air gaps; electric breakdown; electric strength; humidity; impulse testing; insulation testing; power system transients; switchgear testing; 10 kHz; 19 kHz; 20 kHz; 4.2 kHz; 40 C; 5.3 kHz; 8 to 30 cm; air gaps breakdown; bidirectional voltages; breakdown strength; humidity effects; insulation breakdown tests; oscillatory switching impulse voltages; rod-plane gaps; unidirectional voltages; Air gaps; Bidirectional control; Breakdown voltage; Electric breakdown; Frequency; Humidity; IEC standards; Inductance; Surges; Voltage-controlled oscillators;
Conference_Titel :
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location :
Montreal, Que.
Print_ISBN :
0-7803-3531-7
DOI :
10.1109/ELINSL.1996.549346