DocumentCode :
303490
Title :
Partial discharge diagnostics for DC equipment
Author :
Morshuis, Peter ; Hoogenraad, Gerard
Author_Institution :
High Voltage Lab., Delft Univ. of Technol., Netherlands
Volume :
1
fYear :
1996
fDate :
16-19 Jun 1996
Firstpage :
407
Abstract :
Partial discharges (PD) are an indication of weak spots in the insulation of DC high voltage equipment. For AC equipment, classification of the type of defect can be achieved if statistical tools are used on the PD phase distributions. In this paper, the authors propose the use of a similar technique for classification at DC voltage. One major adjustment has to be made: the phase angle used at AC voltage has to be replaced by the time between discharges at DC voltage. This method has been tried on artificial defects with success. Both the method and the test results are presented
Keywords :
electric breakdown; insulation testing; partial discharges; power apparatus; statistical analysis; DC high voltage equipment; PD phase distributions; insulation breakdown tests; insulation weak spots; partial discharge diagnostics; statistical tools; time between discharges; Databases; Fingerprint recognition; Histograms; Insulation; Laboratories; Partial discharge measurement; Partial discharges; Phase detection; Testing; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location :
Montreal, Que.
ISSN :
1089-084X
Print_ISBN :
0-7803-3531-7
Type :
conf
DOI :
10.1109/ELINSL.1996.549367
Filename :
549367
Link To Document :
بازگشت