DocumentCode :
30452
Title :
Investigation on Voltage Sags Caused by DG Anti-Islanding Protection
Author :
Trindade, Fernanda C. L. ; do Nascimento, Klaus V. ; Vieira, Jose Carlos
Author_Institution :
Department of Electrical Energy Systems, University of Campinas (UNICAMP), Brazil
Volume :
28
Issue :
2
fYear :
2013
fDate :
Apr-13
Firstpage :
972
Lastpage :
980
Abstract :
This paper investigates the voltage sag caused by distributed generation anti-islanding protection. This is a new power-quality concern associated with distributed generation expansion. Anti-islanding protection aims to disconnect distributed generators immediately after the opening of a recloser. As a consequence, after the reclosing operation, voltage sag will occur in some parts of the distribution system, since the loads are energized immediately but the generators are no longer present. In this context, this work presents the findings on our investigations about this problem. The results show that the resulting voltage sag level can violate power-quality limits. Thus, a set of indices has been introduced to characterize the severity of the voltage sag, and a load flow-based method has been proposed to predict the phenomenon. Sensitivity studies are also conducted in order to identify some key factors that influence this type of voltage depression.
Keywords :
Delay effects; Generators; Indexes; Power quality; Regulators; Voltage control; Voltage fluctuations; Anti-islanding protection; distributed generation; power quality (PQ); voltage sag;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2012.2237419
Filename :
6420998
Link To Document :
بازگشت