  • Abstract
    The extrapolation method for the error test of the current transformer is to tests the current transformer on-site as a voltage transformer with the same error, which firstly test the error, admittance and other parameters of the trans-former at 200%to 1000%rated voltage or current, then test the admittance at 1%to 120%rated voltage or current, and finally achieves the error through the calculation. Its application will bring a great influence on the test of the current transformer on-site.
  • Keywords
    current transformers; extrapolation; power transformer testing; current transformer testing; error test; low voltage extrapolation method; voltage transformer; Admittance; Circuit faults; Current measurement; Current transformers; Measurement uncertainty; Voltage measurement; Voltage transformers; current transformer; error; extrapolation method; voltage transformer;