DocumentCode
3046391
Title
Hidden failures in protection systems and their impact on wide-area disturbances
Author
Elizondo, David C. ; De La Ree, J. ; Phadke, Arun G. ; Horowitz, Stan
Author_Institution
Bradley Dept. of Electr. Eng., Virginia Polytech. Inst. & State Univ., Blacksburg, VA, USA
Volume
2
fYear
2001
fDate
2001
Firstpage
710
Abstract
This paper explores hidden failures in protection systems, which have been identified as key contributors in the cascading of power system wide-area disturbances. The original definition of hidden failure, which is a failure that remains undetected and is uncovered by another system event, is included as are the developments of hidden failure sequence of events and a methodology for hidden failure identification. This method is based on protection element functionality defects (PEFD). Hidden failures modes are developed based on the relaying implementation for primary protection, back-up protection and special protection systems. Wide-area disturbances based on North American Reliability Council (NERC) reports are analyzed and hidden failures are identified employing the developed methodology. The mechanisms in the wide-area disturbances are summarized. Regions of vulnerability and areas of consequence are important concepts that identify the critical elements from the point of view of hidden failures
Keywords
failure analysis; power system faults; power system protection; power system relaying; power system reliability; relay protection; North American Reliability Council; consequence areas; critical elements identification; protection element functionality defects; protection system hidden failures; vulnerability regions; wide-area disturbances impact; Current transformers; Failure analysis; Power engineering; Power system analysis computing; Power system faults; Power system protection; Power system relaying; Protective relaying; Senior members; Student members;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Winter Meeting, 2001. IEEE
Conference_Location
Columbus, OH
Print_ISBN
0-7803-6672-7
Type
conf
DOI
10.1109/PESW.2001.916941
Filename
916941