• DocumentCode
    3046417
  • Title

    Panel session on data for modeling system transients insulated cables

  • Author

    Gustavsen, Bjørn

  • Author_Institution
    SINTEF Energy Res., Trondheim, Norway
  • Volume
    2
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    718
  • Abstract
    The available EMTP-type programs have dedicated support routines (cable constants) for calculating an electric representation of cable systems in terms of a series impedance matrix Z and a shunt admittance matrix Y, based on cable data defined by geometry and material properties. Z and Y are then used as the basic input for the various cable models applied in time domain transient simulations. This paper describes necessary procedures for converting the available cable data into a new set of data which can be used as input for cable constants. In particular, the paper shows how to handle the semiconducting screens of single core coaxial type cables. In situations where the cable plays an important role in the transient simulation, the user should also consider obtaining a specimen of the cable in order to verify the geometrical data provided by the manufacturer. The recommendations in this paper are supported by field test results
  • Keywords
    EMTP; matrix algebra; power cable insulation; power system analysis computing; power system transients; time-domain analysis; EMTP; cable constants; recommendations; semiconducting screens; series impedance matrix; shunt admittance matrix; single core coaxial type cables; support routines; time domain transient simulations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Winter Meeting, 2001. IEEE
  • Conference_Location
    Columbus, OH
  • Print_ISBN
    0-7803-6672-7
  • Type

    conf

  • DOI
    10.1109/PESW.2001.916943
  • Filename
    916943