DocumentCode
3046735
Title
Lightning performances of distribution lines: sensitivity to computational methods and to data
Author
Borghetti, A. ; Nucci, C.A. ; Paolone, M.
Author_Institution
Dept. of Electr. Eng., Bologna Univ., Italy
Volume
2
fYear
2001
fDate
2001
Firstpage
796
Abstract
The contribution deals with the determination of the curves of the annual number of lightning induced flashover vs. the critical impulse flashover voltage of the insulators, used by power engineers for the assessment of the lightning performance of distribution lines. The results obtained with the method proposed by the authors are compared with those dealt with in the IEEE 1410-1997 Guide (distribution lightning performance). The two methods differ for (a) the models adopted for the evaluation of the induced voltages and (b) for the adopted statistical approach. Reasons for differences in the results predicted by the two methods are illustrated and justified, and the parameters that play the major role in the inference of the curves are identified
Keywords
flashover; insulators; lightning; power distribution lines; power distribution protection; sensitivity analysis; IEEE 1410-1997 Guide; computational methods sensitivity; critical impulse flashover voltage; distribution lightning performance; distribution lines; insulators; lightning induced flashover; lightning performances; Dielectrics and electrical insulation; Distributed computing; Flashover; Lightning; Performance evaluation; Power engineering and energy; Power engineering computing; Statistical analysis; Surges; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Winter Meeting, 2001. IEEE
Conference_Location
Columbus, OH
Print_ISBN
0-7803-6672-7
Type
conf
DOI
10.1109/PESW.2001.916962
Filename
916962