Thermal calculations for buried gas-insulated transmission lines (GIL) and XLPE-cable
Author
Koch, H. ; Chakir, A.
Author_Institution
EV HGIL, Siemens AG, Erlangen, Germany
Volume
2
fYear
2001
fDate
2001
Firstpage
857
Abstract
The requirements of transmitting high amounts of electrical power with an underground transmission system will cause high performance in low system losses. A comparison between the XLPE-cable and the GIL for the same buried parameters shows that the operating temperature by cable is 1.5 to 2 times higher than those of the GIL. This study shows that the GIL meets this requirement better than the cable and is therefore the most reliable solution. A numerical study and long-term test measurements proved the accuracy of the computer code used for this study. The calculated values are verified with measurement carried out with a long duration test at the IPH Test Laboratory in Berlin, Germany. In this long duration test the GIL has been proven through accelerated ageing for an expected life time of 50 years
Keywords
XLPE insulation; ageing; finite element analysis; gaseous insulation; life testing; losses; power cable insulation; power transmission lines; thermal analysis; underground transmission systems; Berlin; FEM; Germany; IPH Test Laboratory; XLPE-cable; accelerated ageing; buried gas-insulated transmission lines; computer code; electrical power transmission; expected life time; long duration test; long-term test measurements; losses; operating temperature; thermal calculations; Conductors; Gas insulated transmission lines; Heat transfer; Insulation; Life testing; Power cables; Power system reliability; Power transmission lines; Propagation losses; Temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Winter Meeting, 2001. IEEE
Conference_Location
Columbus, OH
Print_ISBN
0-7803-6672-7
Type
conf
DOI
10.1109/PESW.2001.916979
Filename
916979
Link To Document