DocumentCode :
3047604
Title :
Improved transient hot-spot temperature calculation method of high voltage bushings
Author :
Ko, C. ; Zhang, S.
Author_Institution :
PCore Electr. Co., Subsidiary of Hubbell Power Syst., LeRoy, NY
fYear :
2008
fDate :
13-15 Aug. 2008
Firstpage :
1
Lastpage :
5
Abstract :
The thermal transient is extremely important when evaluating a high-voltage bushing for overload capability. In this paper, we evaluate the previous methods by others in the effort of calculating bushing thermal transient and introduce our improved direct simulation method using ATP. We verify the validity of our method by comparing the simulation and actual test results which shows both match very well. We also use the method to evaluate the bushing overload condition recommended in IEEE C57.19.100 and the result shows the recommendation is not applicable.
Keywords :
bushings; thermal analysis; transients; ATP simulation method; alternative transients program; bushing overload condition; high voltage bushings; thermal transient; transient hot-spot temperature calculation method; Capacitance; Circuits; Equations; Insulators; Power system modeling; Power system transients; Resistance heating; Steady-state; Temperature; Voltage; ATP; high voltage bushing; hot-spot temperature; thermal transient;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition: Latin America, 2008 IEEE/PES
Conference_Location :
Bogota
Print_ISBN :
978-1-4244-2217-3
Electronic_ISBN :
978-1-4244-2218-0
Type :
conf
DOI :
10.1109/TDC-LA.2008.4641720
Filename :
4641720
Link To Document :
بازگشت