• DocumentCode
    3050271
  • Title

    Dynamic characteristics of high-voltage insulation with metal oxide elements

  • Author

    Nour, H.I.M. ; Sarbaz, F.

  • Author_Institution
    Dept. of Electr. Eng., California State Univ., Long Beach, CA, USA
  • fYear
    1990
  • fDate
    28-31 Oct 1990
  • Firstpage
    575
  • Lastpage
    580
  • Abstract
    The dynamic behavior of an insulation assembly and a metal oxide element is modeled. The multiple arc model, including the characteristics of zinc oxide varistors, was used to evaluate the critical flashover voltage of a dynamic insulator unit. The leakage current through the varistor has the effect of drying the insulator surface, thus increasing the withstand voltage. Nonuniform contamination distribution results in reduction of the critical arc length but has no significant effect on the critical flashover voltage
  • Keywords
    arcs (electric); flashover; insulation testing; insulators; varistors; ZnO; critical arc length; critical flashover voltage; dynamic behavior; high-voltage insulation; insulation assembly; leakage current; metal oxide element; multiple arc model; nonuniform contamination; varistors; withstand voltage; Assembly; Dielectric materials; Dielectrics and electrical insulation; Electric breakdown; Flashover; Pollution; Surface contamination; Surges; Varistors; Zinc oxide;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1990. Annual Report., Conference on
  • Conference_Location
    Pocono Manor, PA
  • Type

    conf

  • DOI
    10.1109/CEIDP.1990.201311
  • Filename