• DocumentCode
    3051725
  • Title

    The optimization of multi-parameter insulation diagnosis

  • Author

    Wu, Kai ; Shen, Wei ; Meng, Yongpeng ; Cao, Wen ; Pan, Cheng ; Cheng, Yonghong ; Zhang, Xiaohong

  • Author_Institution
    State Key Lab. of Electr. Insulation & Power Equip., Xi´´an Jiaotong Univ., Xi´´an, China
  • fYear
    2009
  • fDate
    18-21 Oct. 2009
  • Firstpage
    73
  • Lastpage
    76
  • Abstract
    On the basis of statistical theory, a method to quantitatively determine the reliability of multi-parameter diagnosis and to optimize the algorithm of multi-parameter diagnosis is put forward. This method is based on the statistical law, and concerns correlation between the different parameters. Moreover, as an example, the stator bar of generator (300 MW, 18 kV) is studied. 30 samples were selected from different parts of the practical stator bar of generators, and the parameters of dielectric loss, partial discharge and remaining breakdown voltage (BDV, 50 Hz) of each sample were measured. This method is applied to the estimation BDV of generator bars and the optimized multi-parameter diagnosis algorithm is determined on the basis of actual data. Sk+, tan¿ and ¿C are selected as the optimal parameter group by this method. Comparing with experimental data, it shows that the quantity of parameters is not the more the better. To choose appropriate parameters for assessing insulation condition is important. In order to choose appropriate parameters, two following principles are suggested. (1) It is efficient to select the parameters which have significant correlation with estimation object, as well as to obviate those of limited correlation.( 2) Correlation between parameters should be taken into account. Generally speaking, the degree of correlation between parameters is the lower the better.
  • Keywords
    correlation methods; electric breakdown; insulation testing; optimisation; partial discharges; Sk+ optimal parameter; breakdown voltage estimation; correlation methods; generator stator bar; multiparameter insulation diagnosis optimization; partial discharge; tan¿ optimal parameter; ¿C optimal parameter; Dielectric loss measurement; Dielectric losses; Dielectric measurements; Insulation; Loss measurement; Optimization methods; Partial discharge measurement; Partial discharges; Reliability theory; Stators; Choice of parameters; Insulation diagnosis; Multi-parameter;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2009. CEIDP '09. IEEE Conference on
  • Conference_Location
    Virginia Beach, VA
  • ISSN
    0084-9162
  • Print_ISBN
    978-1-4244-4557-8
  • Electronic_ISBN
    0084-9162
  • Type

    conf

  • DOI
    10.1109/CEIDP.2009.5377795
  • Filename
    5377795