DocumentCode :
3064232
Title :
The analysis and experiment for AC power standard basing on three parameters
Author :
Liu, Min ; Liu, Yanliong
Author_Institution :
Beijing Orient Inst. of Meas. & Test, Chinese Acad. of Space Technol., Beijing, China
fYear :
2004
fDate :
24-27 Aug. 2004
Firstpage :
5
Lastpage :
8
Abstract :
The alternating current (AC) power standard is usually based on the DC power standard by means of an AC/DC thermoelectric comparator, or by means of an A/D converter and digital waveform calculation. In this article, the AC power standard can be based on three parameters - rms AC voltage, rms AC current, and phase between voltage and current. The error analysis proves that the AC power standard can be traced to the AC voltage standard, AC current standard, and phase angle standard. Sine wave distortion was considered as affecting the measurement error in the error analysis. The experimental results of the three parameters method give a conclusion that the uncertainty is below 0.05% above 400 Hz. The three parameters method provide a new path for AC power standard traceability.
Keywords :
electric current measurement; error analysis; harmonic distortion; measurement errors; measurement standards; measurement uncertainty; power factor measurement; power measurement; voltage measurement; 400 Hz; A/D converter; AC current standard; AC power standard traceability; AC voltage standard; AC/DC thermoelectric comparator; DC power standard; error analysis; harmonic distortion; measurement errors; measurement uncertainty; phase angle standard; power factor; sine wave distortion; three parameters method; Analog-digital conversion; Distortion measurement; Error analysis; Frequency; Instruments; Power measurement; Reactive power; Standards development; Testing; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Radio Science Conference, 2004. Proceedings. 2004 Asia-Pacific
Print_ISBN :
0-7803-8404-0
Type :
conf
DOI :
10.1109/APRASC.2004.1422383
Filename :
1422383
Link To Document :
بازگشت