An improvement of AC electrical energy transmission system with series compensation by implementation of controllable shunt reactors
Author :
Belyaev, Andrey N. ; Smolovik, Serguei V.
Author_Institution :
St. Petersburg State Polytech Univ., Russia
Volume :
3
fYear :
2003
fDate :
23-26 June 2003
Abstract :
The application of controllable shunt compensation by the fast-acting transformer type controllable shunt reactors (CSR) is considered for improving the properties of capacitor compensated transmission lines by giving the example of Brazilian North-South 500 kV Interconnection. The reactive power consumed by CSRs in any operation condition is coordinated with the power flow through the line and voltage drop across the capacitors. The transfer capability is limited only by permissible current through the conductors and capacitors. The investigations carried out completely confirm this statement. The type of AC transmission system proposed is strongly recommended to use as a reliable interconnection between the distant power systems.
Keywords :
load flow; power capacitors; power system interconnection; power system transient stability; power transmission lines; reactive power; transmission networks; 500 kV; AC electrical energy transmission system; Brazilian North-South Interconnection; capacitor compensated transmission lines; capacitor voltage drop; controllable shunt reactors; permissible current; reactive power consumption; series compensation; transfer capability; Capacitors; Conductors; Control systems; Inductors; Load flow; Power system interconnection; Power system reliability; Power transmission lines; Reactive power; Shunt (electrical);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN :
0-7803-7967-5
Type :
conf
DOI :
10.1109/PTC.2003.1304526
Filename :
1304526
Link To Document :
بازگشت