Transient short-circuit currents in auxiliary DC installations in power plants and substations
Author
Skok, Srdjan ; Marusic, Ante ; Tesnjak, Sejid
Author_Institution
Dept. of Power Syst., Fac. of Electr. Eng. & Comput., Zagreb, Croatia
Volume
2
fYear
2003
fDate
23-26 June 2003
Abstract
The original contribution of this work is contained in the following statements. A general mathematical model of auxiliary DC installations in power plants was developed in order to be used for analyzing short circuit conditions according to the references K. Albert et al. (1996). It was concluded that the transient state during short circuit has to be taken into account. The essence of this new approach is the new mathematical model which takes into consideration not only resistances, but inductances and capacities of auxiliary DC elements as well as the active network in front of the rectifier. Based on this mathematical model, an original program package was developed and used for analyzing and dimensioning auxiliary DC installations in power plants according to A. Berizzi et al. (1998). The results obtained by means of the program package are relevant for dimensioning all elements of auxiliary DC installations, particularly when protection devices are considered.
Keywords
installation; mathematical analysis; power system analysis computing; power system transients; rectifying circuits; short-circuit currents; substation protection; transient response; active network; auxiliary DC installations; capacities; inductances; mathematical model; power plants; program package; protection devices; rectifier; resistances; selectivity; substations; transient behavior; transient short-circuit currents; transient state; Batteries; Mathematical model; Packaging; Power generation; Power system protection; Power system reliability; Rectifiers; Short circuit currents; Substation protection; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN
0-7803-7967-5
Type
conf
DOI
10.1109/PTC.2003.1304643