DocumentCode
3066514
Title
The prediction of fault currents in a large multiwinding reactor transformer
Author
Reynders, Jan
Author_Institution
Univ. of the Witwatersrand, Johanneburg, South Africa
Volume
2
fYear
2003
fDate
23-26 June 2003
Abstract
The fault currents occurring in power transformers are determined by the leakage reactances within the windings. Where the transformers are used in a phase-shifting mode, there is additional coupling between phases which influences the fault current. This work describes the modelling of the self and mutual inductances in a 90 MVA autotransformer with a tertiary winding, on the assumption that the airgap formed by the transformer window dictates the reluctance of the leakage flux paths. Recordings made during a short-circuit between two phases of the tertiary winding show a remarkably close comparison with the predicted waveforms.
Keywords
autotransformers; fault currents; inductance; transformer windings; 90 MVA; airgap; autotransformer; fault currents; leakage flux; leakage reactances; multiwinding reactor transformer; mutual inductances; phase-shifting mode; power transformers; reluctance; self inductance; tertiary winding; Circuits; Coils; Ducts; Equations; Fault currents; Inductance; Inductors; Magnetic cores; Magnetic flux; Uncertainty;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN
0-7803-7967-5
Type
conf
DOI
10.1109/PTC.2003.1304680
Filename
1304680
Link To Document