Title :
A case study of the application of medium voltage circuit breakers in adverse transient recovery voltage conditions
Author :
Swindler, David Lee
Author_Institution :
Square D Co., Cedar Rapids, IA, USA
Abstract :
Medium voltage circuit breakers are easily misapplied with respect to power system transient recovery voltage (TRV) characteristics. This paper examines one such heavy industrial application in which circuit parameters as originally designed would have exceeded the circuit breakers ratings had corrective measures not been taken. Adverse TRV conditions were being created from more than one source. This paper illustrates this case and discusses the basis of TRV, how TRV is assessed, and alternative actions taken to bring circuits to within the circuit breaker ratings.<>
Keywords :
circuit breakers; industrial power systems; power system protection; power system transients; TRV; adverse transient recovery voltage conditions; application; case study; circuit parameters; heavy industry; medium voltage circuit breakers; power system; ratings; Circuit breakers; Computer aided software engineering; Contacts; Impedance; Interrupters; Medium voltage; Power system transients; Short circuit currents; Transient analysis; Voltage-controlled oscillators;
Conference_Titel :
Pulp and Paper Industry Technical Conference, 1995., Conference Record of 1995 Annual
Conference_Location :
Vancouver, BC, Canada
Print_ISBN :
0-7803-2418-8
DOI :
10.1109/PAPCON.1995.404844