DocumentCode :
3070666
Title :
Diffusion of metal from electrode to vacuum interrupter shield and its effect on electrode construction
Author :
Suzuki, S. ; Matsuo, T. ; Ishibasi, K. ; Yanabu, S.
Author_Institution :
Tokyo Denki University, Tokyo, Japan
Volume :
2
fYear :
2004
fDate :
Sept. 27 2004-Oct. 1 2004
Firstpage :
325
Lastpage :
328
Abstract :
To increase the voltage rating of a vacuum circuit breaker (VCB), diffusion of metallic particles to the vacuum interrupter shield was investigated. Metallic diffusion of axial magnetic electrode construction was extremely small because, due to the effect of the magnetic field, plasma was confined and effectively ionized within it. Electrode erosion of the axial magnetic field electrode during arcing was also extremely small.
Keywords :
Circuits; Current measurement; Electrodes; Interrupters; Particle measurements; Plasma measurements; Plasma temperature; Pollution measurement; Probes; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV. XXIst International Symposium on
Conference_Location :
Yalta, Crimea
ISSN :
1093-2941
Print_ISBN :
0-7803-8461-X
Type :
conf
DOI :
10.1109/DEIV.2004.1422612
Filename :
1422612
Link To Document :
بازگشت