Title :
Diffusion of metal from electrode to vacuum interrupter shield and its effect on electrode construction
Author :
Suzuki, S. ; Matsuo, T. ; Ishibasi, K. ; Yanabu, S.
Author_Institution :
Tokyo Denki University, Tokyo, Japan
fDate :
Sept. 27 2004-Oct. 1 2004
Abstract :
To increase the voltage rating of a vacuum circuit breaker (VCB), diffusion of metallic particles to the vacuum interrupter shield was investigated. Metallic diffusion of axial magnetic electrode construction was extremely small because, due to the effect of the magnetic field, plasma was confined and effectively ionized within it. Electrode erosion of the axial magnetic field electrode during arcing was also extremely small.
Keywords :
Circuits; Current measurement; Electrodes; Interrupters; Particle measurements; Plasma measurements; Plasma temperature; Pollution measurement; Probes; Voltage;
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV. XXIst International Symposium on
Conference_Location :
Yalta, Crimea
Print_ISBN :
0-7803-8461-X
DOI :
10.1109/DEIV.2004.1422612