DocumentCode
3071089
Title
Breaking capacity test of vacuum circuit breaker using synthetic test circuit with current zero forecast
Author
Cai zhiyuan ; Ma Shaohua ; Dai Jun ; Wang Jinghui ; Wang Erzhi
Author_Institution
College of Electrical Engineering, Shenyang University of Technology, Shenyang 11 0023, China. P. R
Volume
2
fYear
2004
fDate
Sept. 27 2004-Oct. 1 2004
Firstpage
387
Lastpage
390
Abstract
In order to test the breaking capacity of vacuum circuit breakers, it is needed to accurately control the synthetic test circuit so as to satisfy the test criterion. For the asymmetry breaking current, it is difficulty to ignite accurately the sphere gaps ahead before zero in an appointed time so as to turn on the arc prolonging current circuit and high voltage circuit. As a result, once asleep the synthetic testing would be unsuccessful. In this paper the synthetic test circuit with current zero forecast is presented. Based on the discussion of the digital signal processing technology, the control circuit has been set up, and the experiment shows a good agreement with the predictions.
Keywords
Circuit breakers; Circuit testing; Current measurement; Current transformers; Frequency; RLC circuits; Switches; Switching circuits; Technology forecasting; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV. XXIst International Symposium on
Conference_Location
Yalta, Crimea
ISSN
1093-2941
Print_ISBN
0-7803-8461-X
Type
conf
DOI
10.1109/DEIV.2004.1422628
Filename
1422628
Link To Document