• DocumentCode
    3076308
  • Title

    Maximum lightning overvoltage location and reliability indices in power system with combined transmission line

  • Author

    Sadeh, J. ; Damchi, Y.

  • Author_Institution
    Electr. Eng. Dept., Islamic Azad Univ., Gonabad, Iran
  • fYear
    2010
  • fDate
    8-10 Nov. 2010
  • Firstpage
    212
  • Lastpage
    217
  • Abstract
    This paper, presents the effect of a cable line on the maximum overvoltage location along cable line and reliability indices in the power system with the combined transmission line (overhead line/cable line). Maximum overvoltage has a vital role in insulators design of high voltage cable. On the other hand, recently with the extension of power systems, maintaining the high degree service reliability is very important. High voltage cable insulations have undesirable effect on power system reliability. Therefore, in this study, the effect of cable line length and the number of span before a cable line are investigated on the amount and location of maximum overvoltage. Furthermore, reliability indices are determined by changing length and age of a cable line in combined transmission line. Results show that cable line length does not change the maximum overvoltage location but has significantly effect on the amount of maximum overvoltage. Also, length and age of cable line effect on power system reliability indices considerably.
  • Keywords
    insulators; overvoltage protection; power system simulation; power transmission lines; power transmission reliability; cable line; combined transmission line; high voltage cable; insulators design; maximum lightning overvoltage location; reliability indices; Power cable insulation; Power cables; Power system reliability; Reliability; Surges; Voltage control; Combined transmission line; overvoltage; power system reliability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition: Latin America (T&D-LA), 2010 IEEE/PES
  • Conference_Location
    Sao Paulo
  • Print_ISBN
    978-1-4577-0488-8
  • Type

    conf

  • DOI
    10.1109/TDC-LA.2010.5762884
  • Filename
    5762884