• DocumentCode
    3081899
  • Title

    The examination and judgment of SF6 Electrical Equipment discharge failure

  • Author

    Xian-sheng Zhuang ; Wei-jian Yao ; Cheng-ji Huang ; WAN, Yu ; Jia-wen Liu ; Xiang Li

  • Author_Institution
    Electr. Power Res. Inst., Guangdong Power Grid Corp., Guangzhou, China
  • fYear
    2008
  • fDate
    10-13 Dec. 2008
  • Firstpage
    1
  • Lastpage
    12
  • Abstract
    This article analyzes two types of SF6 electrical equipment discharge failure: hard failure (the discharge channel mainly consists by SF6 gas insulator only. Electric insulation beyond retrieve after high energy discharge) and soft failure (the discharge channel mainly consists by SF6 gas insulator only or with solid insulator, Electric insulation can be retrieved after high energy discharge); Determine a field fast method to detect the main characteristic gas SO2 and H2S caused by SF6 Electrical equipment discharge failure; Expatiated on the standard of SF6 electrical equipment discharge failure and its application, according to which types positions and current of discharge could be determined.
  • Keywords
    SF6 insulation; discharges (electric); power apparatus; SF6; electric insulation; electrical equipment discharge failure; energy discharge; gas insulator; hard failure; soft failure; solid insulator; Chaos; Condition monitoring; Dielectrics and electrical insulation; Failure analysis; Gas insulation; Plastic insulation; Solids; Sulfur hexafluoride; Surface discharges; Switches; SF6; characteristic component; discharge failure; examination method; judgment standard;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution, 2008. CICED 2008. China International Conference on
  • Conference_Location
    Guangzhou
  • Print_ISBN
    978-1-4244-3373-5
  • Electronic_ISBN
    978-1-4244-3372-8
  • Type

    conf

  • DOI
    10.1109/CICED.2008.5211711
  • Filename
    5211711