DocumentCode
3081899
Title
The examination and judgment of SF6 Electrical Equipment discharge failure
Author
Xian-sheng Zhuang ; Wei-jian Yao ; Cheng-ji Huang ; WAN, Yu ; Jia-wen Liu ; Xiang Li
Author_Institution
Electr. Power Res. Inst., Guangdong Power Grid Corp., Guangzhou, China
fYear
2008
fDate
10-13 Dec. 2008
Firstpage
1
Lastpage
12
Abstract
This article analyzes two types of SF6 electrical equipment discharge failure: hard failure (the discharge channel mainly consists by SF6 gas insulator only. Electric insulation beyond retrieve after high energy discharge) and soft failure (the discharge channel mainly consists by SF6 gas insulator only or with solid insulator, Electric insulation can be retrieved after high energy discharge); Determine a field fast method to detect the main characteristic gas SO2 and H2S caused by SF6 Electrical equipment discharge failure; Expatiated on the standard of SF6 electrical equipment discharge failure and its application, according to which types positions and current of discharge could be determined.
Keywords
SF6 insulation; discharges (electric); power apparatus; SF6; electric insulation; electrical equipment discharge failure; energy discharge; gas insulator; hard failure; soft failure; solid insulator; Chaos; Condition monitoring; Dielectrics and electrical insulation; Failure analysis; Gas insulation; Plastic insulation; Solids; Sulfur hexafluoride; Surface discharges; Switches; SF6; characteristic component; discharge failure; examination method; judgment standard;
fLanguage
English
Publisher
ieee
Conference_Titel
Electricity Distribution, 2008. CICED 2008. China International Conference on
Conference_Location
Guangzhou
Print_ISBN
978-1-4244-3373-5
Electronic_ISBN
978-1-4244-3372-8
Type
conf
DOI
10.1109/CICED.2008.5211711
Filename
5211711
Link To Document