Title :
Analysis of transient dominant frequency signal for single-phase earthed fault based on prony algorithm
Author :
Zhang, Xin Hui ; Fan, Shu Xian ; Duan, Hao ; Bing-yin Xu
Author_Institution :
Sch. of Electr. & Electron. Eng., Shandong Univ. of Technol., Zibo, China
Abstract :
The fact of a dominant resonance frequency existed in the transient process of short-circuit fault is discovered by analyzing transient characteristics of single-phase earthed fault. At this frequency, the amplitude of zero modal current in faulty feeder is much larger than that in healthy feeder, and their polarity is approximately opposite. Transient dominant frequency zero modal current in faulty feeder is 90deg lagged behind zero modal voltage of bus bar, while for healthy feeder it is 90deg leading zero modal voltage of bus bar. Vast simulations under diverse fault conditions have been done by using ATP program. The transient dominant frequency signal is extracted based on Prony algorithm and the corresponding fit data and wave-form is obtained, which completely proved the above conclusions.
Keywords :
earthing; fault diagnosis; short-circuit currents; transient analysis; Prony algorithm; bus bar; faulty feeder; short-circuit fault; simulation; single-phase earthed fault; transient dominant frequency signal analysis; transient process; zero modal current; zero modal voltage; Algorithm design and analysis; Frequency conversion; Power system reliability; Power system transients; Resonance; Resonant frequency; Signal analysis; Signal processing; Transient analysis; Voltage; Non-solidly grounded system; Prony algorithm; dominant resonance frequency; faulty feeder selection; single-phase earthed fault;
Conference_Titel :
Electricity Distribution, 2008. CICED 2008. China International Conference on
Conference_Location :
Guangzhou
Print_ISBN :
978-1-4244-3373-5
Electronic_ISBN :
978-1-4244-3372-8
DOI :
10.1109/CICED.2008.5211810