Three-Phase Fault Detection During Power Swing by Transient Monitor
Author
Khodaparast, Jalal ; Khederzadeh, Mojtaba
Author_Institution
Fac. of Electr. & Comput. Eng., Shahid Beheshti Univ., Tehran, Iran
Volume
30
Issue
5
fYear
2015
fDate
Sept. 2015
Firstpage
2558
Lastpage
2565
Abstract
Distance relays are immune to inadvertent operation during power swings by a block known as “power swing blocking (PSB)”. Its main function is discriminating faults from power swings. However, if a fault occurs during a power swing, PSB should be de-blocked and let the distance relay to operate normally and clear the fault accordingly. Meanwhile, discrimination of a three-phase fault from a power swing is the most difficult task due to their likelihood. This paper proposes a new method to overcome this issue by monitoring the transient period established in the process of current dynamic phasor estimation. In this regard, transient monitor (TM) index, which is the difference between the estimated current samples regenerated from the calculated dynamic phasors and the actual sample values, is used to distinguish the fault from the power swing. Fourier-Taylor transformation is applied to estimate the dynamic phasor of the current signal. Simulation results verify the inherent potential of the proposed method to overcome the issue.
Keywords
Fourier transforms; fault diagnosis; phasor measurement; power system faults; power system transients; Fourier-Taylor transformation; current dynamic phasor estimation; fault discrimination; power swing blocking; three-phase fault detection; transient monitor index; transient period monitoring; Estimation; Fault detection; Impedance; Monitoring; Power system dynamics; Protective relaying; Transient analysis; Distance relay; dynamic phasor; power swing blocking; three-phase fault; transient monitor;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2014.2365511
Filename
6949158
Link To Document