DocumentCode
3094427
Title
10kV straight line fault location based on “Signal injection method”
Author
Jiansheng, Li ; Jun, Liang
Author_Institution
Sch. of Electr. Eng., ShanDong Univ., Jinan, China
Volume
2
fYear
2011
fDate
8-9 Sept. 2011
Firstpage
512
Lastpage
515
Abstract
In distribution power systems, single-phase earth-faults usually happen. With the development of network automation and the rise of power supply quality of users, how to remove the faults quickly and restore normal power supply becomes people´s concern. The proposed method of “Signal injection method” and the device of small current grounding location solve the problem of fault line selection, but fault location problem still exists. Based on the fault line selection, this paper analyzes the voltage and current of the detected signals and deduces the fault distance formula. Matlab/Simulink simulations verify the accuracy of this method. This method isn´t affected by load and arc extinction coil, influenced little by the ground resistance, and has high accuracy.
Keywords
earthing; fault location; power distribution faults; power supply quality; Matlab-Simulink simulations; arc extinction coil; distribution power systems; fault distance formula; fault line selection; ground resistance; network automation; power supply quality; signal injection method; single-phase earth-faults; small current grounding location; straight line fault location; voltage 10 kV; Automation; Circuit faults; Electrical engineering; Fault location; Grounding; Resistance; Signal injection method; distribution power system; fault location; one-phase ground fault;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering and Automation Conference (PEAM), 2011 IEEE
Conference_Location
Wuhan
Print_ISBN
978-1-4244-9691-4
Type
conf
DOI
10.1109/PEAM.2011.6134987
Filename
6134987
Link To Document