Shielding Failure Lightning Protection of 500kV Quadruple-circuit Transmission Lines on the Same Tower
Author
Shifeng, Yu ; Jiangjun, Ruan
Author_Institution
Sch. of Electr. Eng., Wuhan Univ., Wuhan
fYear
2007
fDate
24-28 June 2007
Firstpage
1
Lastpage
4
Abstract
The paper analyzes the performance of shielding failure lightning protection of 500kV quadruple-circuit overhead ac transmission lines on the same tower with revised EGM method and discusses the shielding effect of ground wires to phase conductors. Calculating the shielding failure trip out rate and modeling reasonably based on the analysis of tower style. The relationships between trip out rate and the influence factors such as tower height, protection angle, ground obliquity and striking distance factor are achieved. A conclusion is drawn that the shielding failure rate will turn larger when tower height, protection angle, ground obliquity become larger and the striking distance factor becomes smaller. The calculation and analysis results show that negative protection angle and lower tower height are effective to improve the performance of shielding failure of 500kV quadruple-circuit transmission lines on the same tower.
Keywords
lightning protection; shielding; transmission lines; quadruple-circuit transmission lines; shielding failure lightning protection; voltage 500 kV; Conductors; Failure analysis; Flashover; Lightning protection; Performance analysis; Poles and towers; Power overhead lines; Probability; Transmission lines; Wires; electric geometry model (EGM); ground obliquity; quadruple-circuit on the same tower; shielding failure; striking distance factor;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2007. IEEE
Conference_Location
Tampa, FL
ISSN
1932-5517
Print_ISBN
1-4244-1296-X
Electronic_ISBN
1932-5517
Type
conf
DOI
10.1109/PES.2007.385734
Filename
4275500
Link To Document