    Frequency response analysis of power transformer winding deformation based on a hybrid model

  • Author

    Ji, T.Y. ; Tang, W.H. ; Wu, Q.H.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Liverpool, Liverpool, UK
  • Volume
    3
  • fYear
    2011
  • fDate
    8-9 Sept. 2011
  • Firstpage
    144
  • Lastpage
    147
  • Abstract
    This paper uses a hybrid model of a disc-type transformer winding, which is based on traveling wave and multi-conductor transmission line (MTL) theories, for frequency response analysis (FRA) of winding deformation and measurement parameter influence. Two types of deformation have been simulated by changing the values of the corresponding parameters and the frequency range of FRA is extended to 10 MHz. Various scenarios have been included in the simulation studies, which show that winding deformation can be reflected in frequency response by changing certain parameters of the hybrid model. Simulation results also suggest that the two types of change can be more easily detected in different frequency ranges, respectively.
  • Keywords
    multiconductor transmission lines; power transformers; transformer windings; disc-type transformer winding; frequency 10 MHz; frequency response analysis; measurement parameter influence; multi-conductor transmission line; power transformer winding deformation; traveling wave; Analytical models; Deformable models; Frequency response; Mathematical model; Power transformers; Resonant frequency; Windings; Frequency response analysis (FRA); disc-type transformer model; transformer winding deformation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering and Automation Conference (PEAM), 2011 IEEE
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4244-9691-4
  • Type

    conf

  • DOI
    10.1109/PEAM.2011.6135034
  • Filename
    6135034