DocumentCode
3099134
Title
Analysis and Simulation of Monopolar Grounding Fault in Bipolar HVDC Transmission System
Author
Li, Hua ; Lin, Fuchang ; He, Junjia ; Lu, Yuxin ; Ye, Huisheng ; Zhang, Zhigang
Author_Institution
Coll. of Electr. & Electron. Eng., HuaZhong Univ. of Sci. & Technol., Wuhan
fYear
2007
fDate
24-28 June 2007
Firstpage
1
Lastpage
5
Abstract
The paper analyses the monopolar grounding fault in bipolar HVDC system with phase-modal transformation method. Initial jumping voltage and maximum voltage on health pole with different kinds of termination are deduced by establishing the modal circuit under the fault. Simulation results show a grounding fault in the middle of the line exhibiting maximum voltage with value of 1.54 p.u, which agrees well with the theoretical value. And the maximum voltage decreases with the increasing grounding resistance. The inductance of the reactor influences the maximum voltage on health line a little.
Keywords
HVDC power transmission; earthing; bipolar HVDC transmission system; grounding resistance; health pole; monopolar grounding fault; phase-modal transformation; Analytical models; Circuit faults; Grounding; HVDC transmission; Inductance; Inductors; Insulation; Transmission line matrix methods; Transmission line theory; Voltage control; Bipolar HVDC system; Monopolar grounding fault; Phase-modal transformation method;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2007. IEEE
Conference_Location
Tampa, FL
ISSN
1932-5517
Print_ISBN
1-4244-1296-X
Electronic_ISBN
1932-5517
Type
conf
DOI
10.1109/PES.2007.385955