DocumentCode :
3101364
Title :
Three-Phase Observer-based Low Distortion Grid Current Controller Using an LCL Output Filter
Author :
Bolsens, B. ; De Brabandere, K. ; Van den Keybus, J. ; Driesen, J. ; Belmans, R.
Author_Institution :
ESAT, Katholieke Univ. Leuven, Heverlee
fYear :
2005
fDate :
16-16 June 2005
Firstpage :
1705
Lastpage :
1711
Abstract :
In literature on shunt active power filters and grid current controllers, much effort is done to achieve low current distortions. Some topologies incorporate only an inductor between utility grid and inverter, and this may not suffice to meet regulatory standards on harmonics emission, like IEEE 519 or IEC 61000-3-2 [T]. To reduce the effect of PWM harmonics, more complex output filters are used, such as LC or LCL topologies. These enhanced output filters allow lower switching frequencies. In this paper, a three-phase application is built and tested. After the hardware design of the output stage for a prototype PWM inverter, the control loop is explained briefly. It consists of a Kalman observer to monitor the three-phase grid voltage (including distortion and unbalance), and the LCL output stage. The 20-state observer vector is used for state feedback. To control the DC link voltage, a fast control loop is designed, for operation as an active front end (AFE), or `active rectifier´, or to provide reactive power, and secondly, a slow controller is treated, which is useful for harmonic grid currents injection. Finally, many measurements show that this observer/controller operates very well (ITHD<1%), even under severely unbalanced three-phase voltage systems (VTHD=3%)
Keywords :
IEC standards; IEEE standards; PWM invertors; active filters; electric current control; inductors; observers; power harmonic filters; state feedback; voltage control; DC link voltage control; IEC 61000-3-2 [T]; IEEE 519; Kalman observer; LC topologies; LCL output filter; PWM harmonics reduction; active front end; harmonic grid currents injection; harmonics emission; low current distortions; low distortion grid current controller; lower switching frequencies; regulatory standards; shunt active power filters; state feedback; state observer vector; three-phase grid voltage monitoring; three-phase observer; unbalanced three-phase voltage systems; utility grid; Active filters; IEC standards; Inductors; Power harmonic filters; Pulse width modulation; Pulse width modulation inverters; Shunt (electrical); Switching frequency; Topology; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 2005. PESC '05. IEEE 36th
Conference_Location :
Recife
Print_ISBN :
0-7803-9033-4
Type :
conf
DOI :
10.1109/PESC.2005.1581860
Filename :
1581860
Link To Document :
بازگشت