• DocumentCode
    3103322
  • Title

    Series Connected IGCT based High Power Three-Level Neutral Point Clamped Voltage Source Inverter Pole for FACTS Applications

  • Author

    Bhattacharya, Subhashish

  • Author_Institution
    Siemens Power Transmission & Distribution, NC
  • fYear
    2005
  • fDate
    16-16 June 2005
  • Firstpage
    2315
  • Lastpage
    2321
  • Abstract
    This paper reports requirements, issues and design considerations for high power three-level neutral point clamped (NPC) inverter pole. Dynamic voltage sharing issues, viability and advantages of series connected 4.5 kV, 4 kA IGCT for high power 12 MVA three-level NPC inverter pole are investigated. IGCT turn-off tests at high DC voltage and rated current are used for snubber design and inverter pole clamp design, and to verify simulation results. Experimental results are presented for a two 12 MVA three-level NPC inverter poles operated as H-bridge with three series connected 4.5 kV, 4 kA IGCT per switch
  • Keywords
    bridge circuits; flexible AC transmission systems; invertors; snubbers; thyristor applications; 12 MVA; 4 kA; 4.5 kV; FACTS applications; H-bridge; dynamic voltage sharing; inverter pole clamp design; neutral point clamped voltage source inverter pole; series connected IGCT; snubber design; Clamps; Diodes; Flexible AC transmission systems; Inverters; Snubbers; Switches; Testing; Thyristors; Valves; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Specialists Conference, 2005. PESC '05. IEEE 36th
  • Conference_Location
    Recife
  • Print_ISBN
    0-7803-9033-4
  • Type

    conf

  • DOI
    10.1109/PESC.2005.1581955
  • Filename
    1581955