DocumentCode
3104098
Title
Voltage Regulation Performance of a Shunt Active Filter Intended for Installation on a Power Distribution System
Author
Fujita, Hideaki ; Akagi, Hirofumi
Author_Institution
Dept. of Electr. Eng., Tokyo Inst. of Technol.
fYear
2005
fDate
16-16 June 2005
Firstpage
2578
Lastpage
2584
Abstract
This paper discusses a shunt active filter intended for installation on a power distribution system, with focus on voltage regulation capability. The active filter has capability of regulate the distribution-line voltage by means of adjusting its reactive power. Theoretical analysis investigates the dynamic performance of harmonic damping and voltage regulation as well as computer simulation does. As a result, it is clarified that a harmonic detection error may increase the voltage fluctuations in transient states. A new compensation method is proposed to reduce the voltage fluctuations in transient states. Experimental results show that the proposed method makes it possible to reduce the voltage fluctuation in transient states
Keywords
active filters; damping; distribution networks; installation; power harmonic filters; voltage control; compensation method; distribution-line voltage; harmonic damping; harmonic detection error; installation; power distribution system; shunt active filter; voltage fluctuations reduction; voltage regulation; Active filters; Computer simulation; Damping; Harmonic analysis; Performance analysis; Power distribution; Power harmonic filters; Reactive power; Voltage control; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Specialists Conference, 2005. PESC '05. IEEE 36th
Conference_Location
Recife
Print_ISBN
0-7803-9033-4
Type
conf
DOI
10.1109/PESC.2005.1581996
Filename
1581996
Link To Document