DocumentCode :
3104116
Title :
Sustained response of unbalanced electric system represented through three-phase two-port networks
Author :
Zevallos, M.E. ; Tavares, M.C.
Author_Institution :
Dept. of Electr. & Electron. Eng., Fed. Inst. of Bahia (IFBA), Salvador, Brazil
fYear :
2012
fDate :
7-10 May 2012
Firstpage :
1
Lastpage :
8
Abstract :
This paper proposes the use of three-phase two ports elements to obtain the sustained response of unbalanced electric power system. Representations of three-phase two-ports networks for various types of elements of the electrical power system are described. The methodology is applied to identify the optimum neutral reactor that minimizes the secondary arc current in a transmission system, thus enabling the single-phase auto-reclosing switching implementation.
Keywords :
arcs (electric); power transmission; reactors (electric); optimum neutral reactor; secondary arc current; single-phase auto-reclosing switching; three-phase two-port networks; transmission system; unbalanced electric power system; Admittance; Circuit breakers; Impedance; Inductors; Shunt (electrical); Transmission line matrix methods; Cascade Association; Sustained Response; Three-phase Two-port Network; Unbalanced System;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition (T&D), 2012 IEEE PES
Conference_Location :
Orlando, FL
ISSN :
2160-8555
Print_ISBN :
978-1-4673-1934-8
Electronic_ISBN :
2160-8555
Type :
conf
DOI :
10.1109/TDC.2012.6281563