Title :
A review on chemical diagnosis techniques for transformer paper insulation degradation
Author :
Norazhar, Abu Bakar ; Abu-Siada, A. ; Islam, Shariful
Author_Institution :
Dept. of Electr. & Comput. Eng., Curtin Univ., Perth, WA, Australia
fDate :
Sept. 29 2013-Oct. 3 2013
Abstract :
Energized parts within power transformer are isolated using paper insulation and are immersed in insulating oil. Hence, transformer oil and paper insulation are essential sources to detect incipient and fast developing power transformer faults. Several chemical diagnoses techniques are developed to examine the condition of paper insulation such as degree of polymerization, carbon oxides, furanic compounds and methanol. The principle and limitation of these diagnoses are discussed and compared in this paper.
Keywords :
polymerisation; power transformers; transformer oil; carbon oxides; chemical diagnosis techniques; furanic compounds; insulating oil; methanol; polymerization; power transformer faults; transformer oil; transformer paper insulation degradation; Methanol; Minerals; Oil insulation; Polymers; Power transformer insulation; CO/CO2 ratio; Degree of Polymeriation; Furan analysis; Methanol; Paper insulation;
Conference_Titel :
Power Engineering Conference (AUPEC), 2013 Australasian Universities
Conference_Location :
Hobart, TAS
DOI :
10.1109/AUPEC.2013.6725476