DocumentCode :
3108099
Title :
The method based on a generalized dqk coordinate transform for current detection of an active power filter and power system
Author :
Zhang, B.
Author_Institution :
Electr. Power Coll., South China Univ. of Technol., Guangzhou, China
Volume :
1
fYear :
1999
fDate :
36373
Firstpage :
242
Abstract :
The paper proposes a novel method of current detection for an active power filter and power system. It is based on a generalized dq k coordinate transform. The so called dqk generalized coordinate is defined as the coordinate frame rotated at the angle frequency kω of the kth harmonic current. This method can effectively and accurately detect the fundamental current, its active and reactive components and any term harmonic current component of a three-phase circuit. Simulation results are carried out to verify the method of current detection
Keywords :
active filters; power harmonic filters; transforms; active components; active power filter; angle frequency; current detection; fundamental current; generalized dqk coordinate transform; harmonic current; power system; reactive components; three-phase circuits; Active filters; Circuits; Frequency; Harmonic distortion; Phase detection; Power harmonic filters; Power system harmonics; Power system simulation; Reactive power; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 1999. PESC 99. 30th Annual IEEE
Conference_Location :
Charleston, SC
ISSN :
0275-9306
Print_ISBN :
0-7803-5421-4
Type :
conf
DOI :
10.1109/PESC.1999.789010
Filename :
789010
Link To Document :
بازگشت