• DocumentCode
    3109253
  • Title

    Transformer condition assessment with the Tettex recovery voltage method

  • Author

    Webb, Michael

  • fYear
    1996
  • fDate
    35404
  • Firstpage
    42370
  • Lastpage
    42374
  • Abstract
    All oil-paper transformers contain some water in their solid insulation. The Tettex Recovery Voltage Meter (RVM) is a method for determining the moisture content in the paper so that the effects on dielectric integrity, loading capability and residual life expectancy can be estimated. The author discusses the problems of moisture in paper insulation, the polarisation effects and polarisation spectrum measurement using the Tettex RVM. Practical applications of the method are outlined and it is compared with other methods
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Monitors and Condition Assessment Equipment (Digest No. 1996/186), IEE Colloquium on
  • Conference_Location
    Leatherhead
  • Type

    conf

  • DOI
    10.1049/ic:19961064
  • Filename
    600661