DocumentCode
3122312
Title
Influence of resistance of electric arc on transients due to disconnector switching in air-insulated substations
Author
Carsimamovic, S. ; Bajramovic, Z. ; Veledar, M. ; Ljevak, M. ; Carsimamovic, A. ; Osmokrovic, P.
Author_Institution
Faculty of Electrical Engineering, University of Sarajevo, Bosnia & Herzegovina
Volume
2
fYear
2007
fDate
17-22 June 2007
Firstpage
1840
Lastpage
1843
Abstract
Switching overvoltages due to disconnector switching in air-insulated substations are presented. Shapes and levels of switching overvoltages by means of experimental and computing investigations on 220 kV switchyards of Public Enterprise Elektroprivreda BiH are presented. The influence of resistance of electric arc between the contacts of disconnector is analysed. Computer simulations by means of EMTP-ATP [1] are performed. Differences between the measured and the calculated values were under 4.52% for overvoltage factor, and under 2.56% for overvoltage wave frequency. Comparison of the transient computer simulations with the field measurements showed that calculations could be used for assessment of the transient overvoltages caused by disconnector switching.
Keywords
Computer simulation; Contact resistance; Electric resistance; Electrical resistance measurement; Electromagnetic interference; Frequency; Power generation; Substations; Surges; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Pulsed Power Conference, 2007 16th IEEE International
Conference_Location
Albuquerque, NM
Print_ISBN
978-1-4244-0913-6
Electronic_ISBN
978-1-4244-0914-3
Type
conf
DOI
10.1109/PPPS.2007.4652549
Filename
4652549
Link To Document