DocumentCode
3130127
Title
Evaluation of Stray Losses in Throats of Distribution Transformers Using Finite Element Simulation
Author
Olivares-Galvan, J.C. ; Campero-Littlewood, Eduardo ; Hernandez-Avila, J.L. ; Escarela-Perez, R. ; Adame, S.M. ; Theocharis, A.D.
Author_Institution
Dept. de Energia, Univ. Autonoma Metropolitana-Azcapotzalco, Mexico City, Mexico
fYear
2012
fDate
7-9 Nov. 2012
Firstpage
7
Lastpage
10
Abstract
This paper provides a numerical methodology to quantify the losses produced by induced currents in the metallic ducts (throats) used to enclose the bus bars connecting distribution transformers to switchgears. This calculation is important because some transformer manufacturers in Mexico don´t include throats in the load losses measurement. In particular, it presents the results of simulations made with commercial Finite-Element Software, to quantify the stray losses, originated by the induced currents, in throats of a 2000 kVA distribution transformer. The information provided by transformer´s manufacturers has been used judiciously in the creation of the numerical model.
Keywords
busbars; finite element analysis; power transformers; apparent power 2000 kVA; bus bars; distribution transformers; finite element simulation; finite-element software; induced currents; load losses measurement; metallic ducts; stray losses; switchgears; throats; Conductors; Eddy currents; Finite element methods; Magnetic fields; Numerical models; Power transformers; Surface impedance; Transformer; finite element method; stray losses; throats;
fLanguage
English
Publisher
ieee
Conference_Titel
Andean Region International Conference (ANDESCON), 2012 VI
Conference_Location
Cuenca
Print_ISBN
978-1-4673-4427-2
Type
conf
DOI
10.1109/Andescon.2012.12
Filename
6424109
Link To Document