Title :
The Performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit
Author :
Huang, Xiang ; Sheng Wu ; Fan, Li-juan ; Wang, Chao ; Jun-mei Wu
Author_Institution :
Sch. of Environ. & Chem. Eng., Xi´´an Polytech. Univ., Xi´´an, China
Abstract :
Combining the heat recovery technology of heat pipe and evaporative cooling technology, this article researched a heat recovery heat pipe-type indirect evaporative cooling air-conditioning unit and tested this unit. Based on analyzing we got main perfoprmance factors and best operation parameters. The best ratio of volume of secondary air and primary air is 0.8, the best water delivery is 0.322 m3/h, the efficiency of heat pipe-type indirect evaporative cooler is 70.39%.This research provided reliable reference for the research and development of air-conditioning unit.
Keywords :
air conditioning; cooling; evaporation; heat exchangers; heat pipes; heat recovery; testing; air-conditioning unit; heat recovery type heat pipe; indirect evaporative cooling; performance testing; primary air; secondary air; volume ratio; water delivery; Chemical engineering; Chemical technology; Cooling; Energy consumption; Heat engines; Heat recovery; Performance analysis; Testing; Waste heat; Water heating;
Conference_Titel :
Bioinformatics and Biomedical Engineering (iCBBE), 2010 4th International Conference on
Conference_Location :
Chengdu
Print_ISBN :
978-1-4244-4712-1
Electronic_ISBN :
2151-7614
DOI :
10.1109/ICBBE.2010.5516894