Abstract
Combining the heat recovery technology of heat pipe and evaporative cooling technology, this article researched a heat recovery heat pipe-type indirect evaporative cooling air-conditioning unit and tested this unit. Based on analyzing we got main perfoprmance factors and best operation parameters. The best ratio of volume of secondary air and primary air is 0.8, the best water delivery is 0.322 m3/h, the efficiency of heat pipe-type indirect evaporative cooler is 70.39%.This research provided reliable reference for the research and development of air-conditioning unit.
Keywords
air conditioning; cooling; evaporation; heat exchangers; heat pipes; heat recovery; testing; air-conditioning unit; heat recovery type heat pipe; indirect evaporative cooling; performance testing; primary air; secondary air; volume ratio; water delivery; Chemical engineering; Chemical technology; Cooling; Energy consumption; Heat engines; Heat recovery; Performance analysis; Testing; Waste heat; Water heating;
fLanguage
English
Publisher
ieee
Conference_Titel
Bioinformatics and Biomedical Engineering (iCBBE), 2010 4th International Conference on
Conference_Location
Chengdu
ISSN
2151-7614
Print_ISBN
978-1-4244-4712-1
Electronic_ISBN
2151-7614
Type
conf
DOI
10.1109/ICBBE.2010.5516894
Filename
5516894
Link To Document