• DocumentCode
    3130505
  • Title

    The Performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit

  • Author

    Huang, Xiang ; Sheng Wu ; Fan, Li-juan ; Wang, Chao ; Jun-mei Wu

  • Author_Institution
    Sch. of Environ. & Chem. Eng., Xi´´an Polytech. Univ., Xi´´an, China
  • fYear
    2010
  • fDate
    18-20 June 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Combining the heat recovery technology of heat pipe and evaporative cooling technology, this article researched a heat recovery heat pipe-type indirect evaporative cooling air-conditioning unit and tested this unit. Based on analyzing we got main perfoprmance factors and best operation parameters. The best ratio of volume of secondary air and primary air is 0.8, the best water delivery is 0.322 m3/h, the efficiency of heat pipe-type indirect evaporative cooler is 70.39%.This research provided reliable reference for the research and development of air-conditioning unit.
  • Keywords
    air conditioning; cooling; evaporation; heat exchangers; heat pipes; heat recovery; testing; air-conditioning unit; heat recovery type heat pipe; indirect evaporative cooling; performance testing; primary air; secondary air; volume ratio; water delivery; Chemical engineering; Chemical technology; Cooling; Energy consumption; Heat engines; Heat recovery; Performance analysis; Testing; Waste heat; Water heating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Bioinformatics and Biomedical Engineering (iCBBE), 2010 4th International Conference on
  • Conference_Location
    Chengdu
  • ISSN
    2151-7614
  • Print_ISBN
    978-1-4244-4712-1
  • Electronic_ISBN
    2151-7614
  • Type

    conf

  • DOI
    10.1109/ICBBE.2010.5516894
  • Filename
    5516894