Title :
DTU PMU laboratory development — Testing and validation
Author :
Garcia-Valle, Rodrigo ; Yang, Guang-Ya ; Martin, Kenneth E. ; Nielsen, Arne H. ; Ostergaard, Jacob
Author_Institution :
DTU Electr. Eng. Dept., Centre of Electr. Technol., Lyngby, Denmark
Abstract :
This is a report of the results of phasor measurement unit (PMU) laboratory development and testing done at the Centre for Electric Technology (CET), Technical University of Denmark (DTU). Analysis of the PMU performance first required the development of tools to convert the DTU PMU data into IEEE standard, and the validation is done for the DTU-PMU via a validated commercial PMU. The commercial PMU has been tested from the authors´ previous efforts, where the response can be expected to follow known patterns and provide confirmation about the test system to confirm the design and settings. In a nutshell, having 2 PMUs that observe same signals provides validation of the operation and flags questionable results with more certainty. Moreover, the performance and accuracy of the DTU-PMU is tested acquiring good and precise results, when compared with a commercial phasor measurement device, PMU-1.
Keywords :
IEEE standards; measurement standards; power system measurement; DTU PMU laboratory development; DTU PMU testing; DTU PMU validation; IEEE standard; Technical University of Denmark; phasor measurement unit; Accuracy; Current measurement; Global Positioning System; Phasor measurement units; Power systems; Steady-state; Synchronization; IEEE C37.118; phasor measurement units; synchronised phasor; universal coordinated time (UTC);
Conference_Titel :
Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES
Conference_Location :
Gothenburg
Print_ISBN :
978-1-4244-8508-6
Electronic_ISBN :
978-1-4244-8509-3
DOI :
10.1109/ISGTEUROPE.2010.5638883