The effect of DC offset on instantaneous operating characteristics of low-voltage circuit breakers
Author
Chapman, Francis X. ; Hammonds, Bret
Author_Institution
SPD Technol., USA
Volume
4
fYear
1996
fDate
6-10 Oct 1996
Firstpage
2265
Abstract
This paper addresses the effect of asymmetrical currents on factory adjustments and field verification of low-voltage circuit breaker instantaneous trip units. Both MCCBs and power circuit breakers are pertinent. Factory adjustment of low-voltage circuit breakers, based on test results using asymmetrical current, may cause the circuit breaker instantaneous unit to perform improperly and result in inadequate protection and coordination of electrical system apparatus. Similarly, field testing conducted to verify proper performance of low-voltage circuit breakers, using asymmetrical current, may lead to the erroneous conclusion that the circuit breaker´s instantaneous unit is out of specification. In addition to addressing the difficulties presented by this phenomenon, this paper also proposes an approach to identifying and overcoming these testing difficulties
Keywords
circuit breakers; switchgear testing; DC offset effect; MCCB; asymmetrical currents effects; factory adjustments; field verification; instantaneous operating characteristics; low-voltage circuit breakers; molded case circuit breakers; power circuit breakers; testing difficulties; Circuit breakers; Circuit faults; Circuit testing; Delay effects; Electromechanical sensors; Fault diagnosis; Performance evaluation; Power system protection; Production facilities; System testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Conference, 1996. Thirty-First IAS Annual Meeting, IAS '96., Conference Record of the 1996 IEEE
Conference_Location
San Diego, CA
ISSN
0197-2618
Print_ISBN
0-7803-3544-9
Type
conf
DOI
10.1109/IAS.1996.563889
Filename
563889
Link To Document