Title :
Survey of harmonics measurements in electrical distribution systems
Author :
Tolbert, Leon M. ; Hollis, Harold D. ; Hale, Peyton S.
Author_Institution :
Oak Ridge Nat. Lab., TN, USA
Abstract :
An assessment of the harmonics found in the electrical distribution system of several buildings in the three Department of Energy (DOE) Oak Ridge plants in Tennessee has yielded several conclusions useful in the design of electrical distribution systems. A preliminary survey to determine where significant amounts of harmonic currents or voltages existed in the distribution system was performed at several buildings by comparing readings taken with true root-mean-square (RMS) multimeters and averaging multimeters (nontrue RMS meters). From these measurements and subsequent calculations, facilities that appeared to have significant levels of harmonics present were analyzed with a power analyzer that could record waveforms and give the spectrum and magnitude of harmonics. Among the nonlinear loads for which sample waveforms are illustrated are fluorescent lighting (both magnetic and electronic ballasts), variable frequency drives, switch mode power supplies, and uninterruptible power supplies. A discussion as to how various harmonic waveforms come about as a result of these nonlinear loads is also outlined in this paper
Keywords :
distribution networks; electric current measurement; fluorescent lamps; lamp accessories; multimeters; power system harmonics; power system measurement; switched mode power supplies; uninterruptible power supplies; variable speed drives; voltage measurement; Department of Energy; Oak Ridge plants; Tennessee; electrical distribution systems; electronic ballasts; fluorescent lighting; harmonic currents; harmonic voltages; harmonic waveforms; harmonics assessment; harmonics measurements; magnetic ballasts; nonlinear loads; nontrue RMS meters; power analyzer; switch mode power supplies; true root-mean-square multimeters; uninterruptible power supplies; variable frequency drives; Buildings; Electric variables measurement; Fluorescence; Harmonic analysis; Magnetic analysis; Power measurement; Power system harmonics; Switches; US Department of Energy; Voltage;
Conference_Titel :
Industry Applications Conference, 1996. Thirty-First IAS Annual Meeting, IAS '96., Conference Record of the 1996 IEEE
Conference_Location :
San Diego, CA
Print_ISBN :
0-7803-3544-9
DOI :
10.1109/IAS.1996.563898