Abstract
In a recent authors´ work, a so-called numerical hybrid state model has been introduced. In the present paper, the proposed model is extended for analysis of partial load rejection tests. Time-variant analytical waveforms of phase voltages and the field current following load rejection tests are derived in terms of physical machine parameters using the state model solution of linear system theory. Two load rejection tests (50% and 100%) are performed and comparisons are made between simulation results and actual data obtained from a 4-pole, 1.5-kVA, 208-V, and 60-Hz laboratory machine
Keywords
machine testing; synchronous generators; 1.5 kVA; 208 V; 60 Hz; linear system theory; load rejection analysis; numerical hybrid state model; phase voltage; physical machine parameter; synchronous generator; Circuit testing; Hybrid power systems; Linear systems; Numerical models; Performance evaluation; Power system reliability; Synchronous generators; Synchronous machines; System testing; Voltage; Synchronous generator; hybrid analytical model; partial load rejection tests; simulations and experiments;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Computer Engineering, 2006. CCECE '06. Canadian Conference on
Conference_Location
Ottawa, Ont.
Print_ISBN
1-4244-0038-4
Electronic_ISBN
1-4244-0038-4
Type
conf
DOI
10.1109/CCECE.2006.277528
Filename
4054901
Link To Document