    Analysis of the potential distribution in a relay cell generated by a direct lightning strike in a 500 kV substation

  • Author

    Maolin, Wu ; Xiang, Cui ; Zhongyuan, Zhang

  • Author_Institution
    North China Electr. Power Univ., Hebei, China
  • fYear
    2002
  • fDate
    21-24 May 2002
  • Firstpage
    198
  • Lastpage
    201
  • Abstract
    The protection and controlling devices have been moved into the relay cell in the switchyard from the controlling building in some newly-built 500 kV substations in China. The transient grounding potential rise will be caused in a relay cell by a direct lightning strike in a 500 kV substation and be harmful to the secondary devices. Therefore, it is very important to predict the transient potential distribution in the relay cell. The authors calculated and analyzed the transient grounding potential distribution, found the appropriate mode of the inner grounding grid in the relay cell. Thus, the electromagnetic interference that the protection and controlling devices will suffer from the transient grounding potential rise in the relay cell can be reduced greatly.
  • Keywords
    earth electrodes; lightning protection; relay protection; substation automation; substation protection; China; controlling device; direct lightning strike; inner grounding grid; potential distribution; protection device; relay cell; secondary devices; transient grounding potential distribution; transient grounding potential rise; transient potential distribution; Electromagnetic transients; Frequency; Grounding; Lighting control; Lightning; Protective relaying; Relays; Steel; Substation protection; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetic Compatibility, 2002 3rd International Symposium on
  • Print_ISBN
    0-7803-7277-8
  • Type

    conf

  • DOI
    10.1109/ELMAGC.2002.1177402
  • Filename
    1177402