Title :
Research on improvements of using electronic current transformer on distance protection
Author :
Chen, Qingqian ; Hou, Hui ; You, Dahai ; Yin, Xianggen ; Yao, Zhandong
Author_Institution :
Huazhong Univ. of Sci. & Technol., Wuhan
Abstract :
Traditional magnetic current transformer (CT) always has the problem of saturation, which depresses the accuracy of distance protection´s impedance measurement and shortens its protection zone. Based on this analysis, traditional measures to solve this problem are summarized first, and then the newly developed electronic current transformer (ECT) is introduced as a new way to solve the problem. Because of its high accuracy, high stability, wide frequency band, and most of all, without the problem of magnetic saturation, ECT has become a popular substitute for traditional CT. It can improve the starting unit, phase selecting unit, impedance unit and other functional units of distance protection. Experimental analysis shows that using ECT instead of traditional CT can enhance the operating accuracy and reliability of distance protection greatly.
Keywords :
current transformers; electric impedance measurement; distance protection; electronic current transformer; magnetic current transformer; Circuit faults; Current transformers; Electrical capacitance tomography; Impedance; Magnetic separation; Optical distortion; Optical saturation; Power system protection; Power system stability; Saturation magnetization; Current transformers; Electronic Current Transformer; distance protection; optical fiber transducers; saturation;
Conference_Titel :
Universities Power Engineering Conference, 2007. UPEC 2007. 42nd International
Conference_Location :
Brighton
Print_ISBN :
978-1-905593-36-1
Electronic_ISBN :
978-1-905593-34-7
DOI :
10.1109/UPEC.2007.4468958