Abstract
To ensure distance relay can measure the impedance and trip the fault phase selectively during power swing, it is necessary to study fault classification during power swing. The conventional sequence current and phase-to-phase impedance relay based fault classification scheme has been analyzed to mal-operate in some cases during power swing. In order to overcome the disadvantage, single-phase-to-ground impedance relay and phase-to-phase impedance relay and sequence voltage criterion based improved fault classification scheme is proposed in this paper. The results of ATP digital simulation and dynamic simulation tests indicate that proposed scheme has advantage with origin scheme particularly in fault classification under the condition of power swing.
Keywords
power system relaying; power transmission faults; power transmission protection; ATP digital simulation; conventional sequence current impedance relay; distance relay; fault classification scheme; fault phase; phase-to-phase impedance relay; power swing; single-phase-to-ground impedance relay; Digital relays; Educational institutions; Fault diagnosis; Impedance measurement; Phase measurement; Power engineering and energy; Power measurement; Protection; Protective relaying; Voltage; fault classification; power swing blocking; sequence component; transmission line protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2007. UPEC 2007. 42nd International
Conference_Location
Brighton
Print_ISBN
978-1-905593-36-1
Electronic_ISBN
978-1-905593-34-7
Type
conf
DOI
10.1109/UPEC.2007.4468963
Filename
4468963
Link To Document