DocumentCode :
3149458
Title :
Current transformer saturation detectors for busbar differential protection
Author :
Dashti, H. ; Sanaye-Pasand, M. ; Davarpanah, M.
Author_Institution :
Univ. of Tehran, Tehran
fYear :
2007
fDate :
4-6 Sept. 2007
Firstpage :
338
Lastpage :
343
Abstract :
Busbar differential relays may operate incorrectly due to current transformer (CT) saturation. In this paper two different techniques are suggested to detect CT saturation. The first proposed algorithm is based on the fact that the wave shape of the CT secondary current is changed significantly at the instant of the saturation. Based on this feature, an algorithm which uses second derivative of CT output current is developed. The second proposed method utilizes the zero crossing principle. It compares the predicted and measured zero crossing of the current signal. The proposed method is able to detect even small CT saturation events. A real 400 kV busbar is simulated using PSCAD/EMTDC for evaluating performance of the proposed algorithms. Obtained results demonstrate the precise operation of the both proposed algorithms in different conditions.
Keywords :
busbars; current transformers; power system protection; busbar differential protection; current transformer saturation detector; second derivative; voltage 400 kV; wave shape; zero crossing principle; Circuit faults; Current measurement; Current transformers; Detectors; Event detection; Fault currents; PSCAD; Protection; Protective relaying; Shape; Busbar differential protection; CT saturation detection; Second derivative; Zero-crossing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference, 2007. UPEC 2007. 42nd International
Conference_Location :
Brighton
Print_ISBN :
978-1-905593-36-1
Electronic_ISBN :
978-1-905593-34-7
Type :
conf
DOI :
10.1109/UPEC.2007.4468971
Filename :
4468971
Link To Document :
بازگشت