• DocumentCode
    3153919
  • Title

    Detection of anomalies on substation protection using oscillography relays

  • Author

    Oling, R. ; De Oliveira, H. R P M ; Papaleo, G.K. ; Martinez, M.L.B.

  • Author_Institution
    AES SUL-Distribuidora Gaucha de Energia S/A, Sao Leopoldo, Brazil
  • Volume
    3
  • fYear
    2002
  • fDate
    6-10 Oct. 2002
  • Firstpage
    1719
  • Abstract
    This work elucidates how the authors detected a discoordination case involving overcurrent relays of a feeder and a electric energy substation transformer of AES Sul-Distribuidora Gaucha de Energia concession´s area, originating on the disregarding, on the protection adjust period, of the different load levels of distribution feeders and total current from the substation transformer. If the relays didn´t include an oscillographics option on substation digital protection, this problem probably would not be recognized. Also, the providences to this problem of bad coordination in the company are presented.
  • Keywords
    overcurrent protection; power system measurement; power system protection; power system relaying; relay protection; short-circuit currents; substation protection; Brazil; anomalies detection; distribution feeder; oscillography relays; overcurrent relays; substation protection; transformer; Circuit breakers; Circuit faults; Digital relays; Impedance; Power engineering and energy; Power system faults; Power system protection; Power system relaying; Protective relaying; Substation protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
  • Print_ISBN
    0-7803-7525-4
  • Type

    conf

  • DOI
    10.1109/TDC.2002.1177713
  • Filename
    1177713