DocumentCode
3153919
Title
Detection of anomalies on substation protection using oscillography relays
Author
Oling, R. ; De Oliveira, H. R P M ; Papaleo, G.K. ; Martinez, M.L.B.
Author_Institution
AES SUL-Distribuidora Gaucha de Energia S/A, Sao Leopoldo, Brazil
Volume
3
fYear
2002
fDate
6-10 Oct. 2002
Firstpage
1719
Abstract
This work elucidates how the authors detected a discoordination case involving overcurrent relays of a feeder and a electric energy substation transformer of AES Sul-Distribuidora Gaucha de Energia concession´s area, originating on the disregarding, on the protection adjust period, of the different load levels of distribution feeders and total current from the substation transformer. If the relays didn´t include an oscillographics option on substation digital protection, this problem probably would not be recognized. Also, the providences to this problem of bad coordination in the company are presented.
Keywords
overcurrent protection; power system measurement; power system protection; power system relaying; relay protection; short-circuit currents; substation protection; Brazil; anomalies detection; distribution feeder; oscillography relays; overcurrent relays; substation protection; transformer; Circuit breakers; Circuit faults; Digital relays; Impedance; Power engineering and energy; Power system faults; Power system protection; Power system relaying; Protective relaying; Substation protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN
0-7803-7525-4
Type
conf
DOI
10.1109/TDC.2002.1177713
Filename
1177713
Link To Document